[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936700":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},936700,605,1,"单选题","厂房、仓库消防水枪充实水柱应按（ ）计算。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","7m",false,{"key":16,"text":17,"correct":14},"B","10m",{"key":19,"text":20,"correct":21},"C","13m",true,{"key":23,"text":24,"correct":14},"D","17m","参考《消防给水及消火栓系统技术规范》7.4.12：“室内消火栓栓口压力和消防水枪充实水柱，应符合下列规定：2高层建筑、厂房、库房和室内净空高度超过8m的民用建筑等场所，消火栓栓口动压不应小于0.35MPa，且消防水枪充实水柱应按13m计算；其他场所，消火栓栓口动压不应小于0.25MPa，且消防水枪充实水柱应按10m计算”，故C正确。说明：“高层建筑”已经包括了高层厂房、高层库房（仓库），后面的厂房、仓库也包括了所有的厂房、库房，故所有的厂房、库房（仓库）充实水柱均应按13m计算。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]