[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936698":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936698,605,2,"多选题","采用消防水泵串联分区供水时，宜采用消防水泵转输水箱串联供水方式，并符合下列规定（ ）。",[11,15,18,21,24],{"key":12,"text":13,"correct":14},"A","当采用消防水泵转输水箱串联时，转输水箱的有效储水容积不应小于60m3，转输水箱可作为高位消防水箱",true,{"key":16,"text":17,"correct":14},"B","串联转输水箱的溢流管宜连接到消防水池",{"key":19,"text":20,"correct":14},"C","当采用消防水泵直接串联时，应采取确保供水可靠性的措施，且消防水泵从低区到高区应能依次顺序启动",{"key":22,"text":23,"correct":14},"D","当采用消防水泵直接串联时，应校核系统供水压力，并应在串联消防水泵出水管上设置减压型倒流防止器",{"key":25,"text":26,"correct":27},"E","当采用消防水泵直接串联时，应校核系统供水压力，并应在并联消防水泵出水管上设置增压型倒流防止器",false,"ABCD","参考《消防给水及消火栓系统技术规范》6.2.3：采用消防水泵串联分区供水时，宜采用消防水泵转输水箱串联供水方式，并应符合下列规定：1.当采用消防水泵转输水箱串联时，转输水箱的有效储水容积不应小于60m3，转输水箱可作为高位消防水箱：故A正确。2.串联转输水箱的溢流管宜连接到消防水池；故B正确。3.当采用消防水泵直接串联时，应采取确保供水可靠性的措施，且消防水泵从低区到高区应能依次顺序启动；故C正确。4.当采用消防水泵直接串联时，应校核系统供水压力，并应在串联消防水泵出水管上设置减压型倒流防止器。故D正确，E错误。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]