[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936686":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},936686,605,1,"单选题","机械防烟系统的主要性能参数验收中，打开模拟着火楼层前室、合用前室、消防电梯前室的防火门，对于地上楼梯间，当机械加压送风系统负担层数为18层时，应同时打开（ ）的防火门。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","模拟着火楼层及其下一层",false,{"key":16,"text":17,"correct":18},"B","模拟着火楼层及其上、下一层",true,{"key":20,"text":21,"correct":14},"C","模拟着火楼层及其上一层",{"key":23,"text":24,"correct":14},"D","模拟着火楼层及其上二层","对于地上楼梯间，当机械加压送风系统负担层数小于15层时，同时打开模拟着火楼层及其上一层楼梯间的防火门；当机械加压送风系统负担层数大于等于15层时，同时打开模拟着火楼层及其上、下一层楼梯间的防火门；对于地下楼梯间，同时打开模拟着火楼层楼梯间的防火门；本题为18层，应打开模拟着火楼层及其上、下一层楼梯间的防火门。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]