[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936637":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},936637,605,1,"单选题","消防机构对一座在建的工程进行检查，在对临时发电机房，变、配电房，厨房操作间检查时，结果如下，其中符合规定的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","建筑构件的燃烧性能等级为B1级",false,{"key":16,"text":17,"correct":14},"B","建筑层数为单层，建筑面积为300m2",{"key":19,"text":20,"correct":14},"C","房间内任一点至最近疏散门的距离为15m",{"key":22,"text":23,"correct":24},"D","房间疏散门的净宽度为0．9m",true,"根据《建设工程施工现场消防安全技术规范》GB 50720—20114．2．2，发电机房，变配电房、厨房操作间，锅炉房，可燃材料库房及易燃易爆危险品库房的防火设计应符合下列规定： 1）建筑构件的燃烧性能等级应为A级。A选项错误。 2）层数应为1层，建筑面积不应大于200m2。B选项错误。 3）可燃材料库房单个房间的建筑面积不应超过30m2，易燃易爆危险品库房单个房间的建筑面积不应超过20m2。 4）房间内任一点至最近疏散门的距离不应大于10m，房门的净宽度不应小于0．8m。C选项错误，D选项正确。 本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]