[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936628":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},936628,605,1,"单选题","某建筑高度为120m的在建工程，设有临时中转水池及加压水泵。该中转水池的有效容积不应少于（ ）m3。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","5",false,{"key":16,"text":17,"correct":18},"B","10",true,{"key":20,"text":21,"correct":14},"C","15",{"key":23,"text":24,"correct":14},"D","20","根据《建设工程施工现场消防安全技术规范》GB 50720—20115．3．14，高度超过100m的在建工程，应在适当楼层增设临时中转水池及加压水泵，中转水池的有效容积不应少于10m3，上、下两个中转水池的高差不宜超过100m。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]