[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936527":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936527,605,2,"多选题","消防部门对某高层建筑的消防救援口设置情况进行专项检查，检查后记录的某个救援窗口设置情况如下，其中不符合现行国家工程建设消防技术标准的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","该救援窗口的净高度和净宽度分别为1.10m和1.15m",false,{"key":16,"text":17,"correct":18},"B","该救援窗口下沿距室内地面的高度为1.24m",true,{"key":20,"text":21,"correct":18},"C","该救援窗口与最近一个救援窗口之间的间距为22.5m",{"key":23,"text":24,"correct":14},"D","该救援窗口的位置与消防车登高操作场地相对应",{"key":26,"text":27,"correct":18},"E","该救援窗口在室内设置了明显的标志","BCE","《建筑设计防火规范》（GB 50016-2014），7.2.5 供消防救援人员进入的窗口的净高度和净宽度均不应小于1.0m，下沿距室内地面不宜大于1.2m，间距不宜大于20m且每个防火分区不应少于2个，设置位置应与消防车登高操作场地相对应。窗口的玻璃应易于破碎，并应设置可在室外易于识别的明显标志。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]