[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936462":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936462,605,2,"多选题","在对某民用建筑内设置的机械加压送风系统进行检测时，应检测系统的联动控制功能，根据《火灾自动报警系统设计规范》GB 50116—2013，下列能够联动开启加压送风口的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","加压送风口所在防火分区内的两只独立的火灾探测器的动作信号",true,{"key":16,"text":17,"correct":18},"B","加压送风口所在防火分区内一只火灾探测器与相邻防火分区的一只手动火灾报警按钮的动作信号",false,{"key":20,"text":21,"correct":18},"C","加压送风口所在防火分区内的两只独立的手动火灾报警按钮的动作信号",{"key":23,"text":24,"correct":14},"D","加压送风口所在防火分区内一只火灾探测器与一只手动火灾报警按钮的动作信号",{"key":26,"text":27,"correct":18},"E","加压送风口所在防烟分区内一只火灾探测器与相邻防烟分区的一只手动火灾报警按钮的动作信号","AD","根据《火灾自动报警系统设计规范》GB 50116—20134．5．1-1，应由加压送风口所在防火分区内的两只独立的火灾探测器或一只火灾探测器与一只手动火灾报警按钮的报警信号，作为送风口开启和加压送风机启动的联动触发信号，并应由消防联动控制器联动控制相关层前室等需要加压送风场所的加压送风口开启和加压送风机启动。本题答案为AD。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]