[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936461":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936461,605,2,"多选题","某建筑进入火灾自动报警系统调试阶段，根据现行《火灾自动报警系统施工及验收标准》，触发某报警区域内的一只感烟火灾探测器和一只手报按钮，下列系统中可以动作的是（ ）",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","用于防火分隔中的雨淋阀组",false,{"key":16,"text":17,"correct":14},"B","消火栓系统中的消防水泵",{"key":19,"text":20,"correct":21},"C","全楼疏散通道的应急照明和疏散指示系统",true,{"key":23,"text":24,"correct":21},"D","该报警区域内所有常开防火门",{"key":26,"text":27,"correct":14},"E","全楼所有的声光警报器同时启动，且与应急广播交替循环","CD","根据《火灾自动报警系统施工及验收标准》GB50166-2019， 防火分隔中的雨淋阀组，触发信号为同一报警区域内的两只感温探测器，A错误。消火栓水泵的触发信号为报警区域内的两只探测器或一只探测器一只手报按钮，同时消火栓按钮，B错误。声光警报与应急广播系统收到与逻辑信号后，启动的是该报警区域内的声光警报器和应急广播的启动，不是全楼，E错误。选项E，考查的是2019版《火灾自动报警系统施工及验收标准》4.12.6条 ，此条的目的是为了方便调试提出的简化要求，不是考查《火灾自动报警设计规范》4.8.1条，因此E选项不正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]