[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936454":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},936454,605,1,"单选题","下列关于火灾自动报警系统中组件安装的说法，错误的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","点型探测器倾斜安装时，倾斜角度不应大于45°",false,{"key":16,"text":17,"correct":14},"B","同一报警区域内的模块应集中安装在金属箱内",{"key":19,"text":20,"correct":14},"C","手动火灾报警按钮的连接导线应留有不小于150mm的余量",{"key":22,"text":23,"correct":24},"D","光警报器与疏散指示标志安装在同一面墙上时，距离不应小于1．5m",true,"根据《火灾自动报警系统施工及验收规范》GB 50166—2019 探测器宜水平安装，当确需倾斜安装时，倾斜角不应大于45°，A选项正确；同一报警区域内的模块宜集中安装在金属箱内，B选项正确；手动火灾报警按钮的连接导线应留有不小于150mm的余量，且在其端部应有明显标志，C选项正确；光警报器与消防应急疏散指示标志不宜在同一面墙上，安装在同一面墙上时，距离应大于1m，D选项错误。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]