[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936451":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},936451,605,1,"单选题","消防技术检测服务机构对某建筑内火灾探测器的安装质量进行检查，结果如下，其中不符合规范规定的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","安装在宽度为2．5m的内走道顶棚上的点型感烟探测器的间距为12m",false,{"key":16,"text":17,"correct":14},"B","安装在顶棚上的点型感烟探测器距多孔送风顶棚孔口的水平距离为1．2m",{"key":19,"text":20,"correct":21},"C","安装在办公室的点型感烟火灾探测器距梁边的距离为0．4m",true,{"key":23,"text":24,"correct":14},"D","安装在办公室的点型感烟火灾探测器至空调送风口边的水平距离为1.6m","根据《火灾自动报警系统施工及验收规范》（GB 50166-2019）在宽度小于3m的内走道顶棚上设置点型探测器时，宜居中布置，感温火灾探测器的安装间距不应超过10m，感烟火灾探测器的安装间距不应超过15m，探测器至端墙的距离，不应大于探测器安装间距的1／2，A选项正确；点型探测器至空调送风口边的水平距离不应小于1．5m,D选项正确；至多孔送风顶棚孔口的水平距离，不应小于0．5m，B选项正确；探测器至墙壁、梁边的水平距离，不应小于0．5m，C选项错误；本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]