[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936450":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},936450,605,1,"单选题","当敷设在顶棚下方的线型差温火灾探测器至顶棚距离宜为（ ）m,相邻探测器之间的水平距离不宜大于（ ）m。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","0.5，1",false,{"key":16,"text":17,"correct":14},"B","0.1，2",{"key":19,"text":20,"correct":14},"C","1，5",{"key":22,"text":23,"correct":24},"D","0.1，5",true,"《火灾自动报警系统施工及验收规范》（GB 50166-2019）3.3.8 敷设在顶棚下方的线型差温火灾探测器至顶棚距离宜为0.1m，相邻探测器之间的水平距离不宜大于5m，探测器至墙壁距离宜为1.0m～1.5m.答案为D.",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]