[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936449":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},936449,605,1,"单选题","下列关于引入火灾自动报警控制器的电缆和导线安装要求的说法中，错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","控制器内端子板的每个接线端接线不能超过2根",false,{"key":16,"text":17,"correct":18},"B","控制器的主电源严禁与消防电源直接相连",true,{"key":20,"text":21,"correct":14},"C","接到端子板的电缆芯线和导线，应留有不小于200mm的余量",{"key":23,"text":24,"correct":14},"D","导线穿管、线槽后，应将管口、槽口封堵","《火灾自动报警系统施工及验收规范》（GB 50166-2019）3.3.3 控制器的主电源应有明显的永久性标志，并应直接与消防电源连接，严禁使用电源插头。控制器与其外接备用电源之间应直接连接。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]