[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936447":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},936447,605,1,"单选题","引入火灾报警控制器的电缆或导线，应留有不小于（ ）mm的余量。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","100",false,{"key":16,"text":17,"correct":14},"B","150",{"key":19,"text":20,"correct":21},"C","200",true,{"key":23,"text":24,"correct":14},"D","250","根据《火灾自动报警系统施工及验收规范》GB 50166—2019 3．3．2，引入控制器的电缆或导线，应符合下列要求： 1）配线应整齐，不宜交叉，并应固定牢靠。 2）电缆芯线和所配导线的端部，均应标明编号，并与图纸一致，字迹应清晰且不易褪色。 3）端子板的每个接线端，接线不得超过2根。 4）电缆芯和导线，应留有不小于200mm的余量。 5）导线应绑扎成束。 6）导线穿管、线槽后，应将管口、槽口封堵。 本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]