[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936439":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936439,605,2,"多选题","消防技术服务机构对某建筑设置的临时高压消防给水系统进行检查，打开试验管放水，消防水泵出水干管上的低压压力开关动作，消防联动控制器上显示低压压力开关动作，但消防水泵没有启动，对此现象原因进行分析，下列说法正确的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","低压压力开关损坏",false,{"key":16,"text":17,"correct":18},"B","低压压力开关至消防水泵控制柜之间的线路断路",true,{"key":20,"text":21,"correct":18},"C","消防水泵控制柜处于手动控制状态",{"key":23,"text":24,"correct":14},"D","消防联动控制器处于手动控制状态",{"key":26,"text":27,"correct":18},"E","消防水泵损坏","BCE","本题需了解整个消防水泵的启动流程及消防联动控制原理。 Ａ选项，如果低压压力开关损坏，则不会动作，题中动作，所以不可能是压力开关损坏 Ｂ选项，联动控制器上显示压力开关的动作信号，只能说明反馈线路没有问题。但控制信号与反馈信号不是同一线路。泵没有启动可能是控制线路损坏。 Ｃ选项，消防水泵控制柜处于手动控制状态，无法自动启动，也有可能 Ｄ选项，水泵启动不收消防联动控制器处于手动或自动状态的影响。 Ｅ选项，消防水泵损坏无法启动，正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]