[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936435":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936435,605,2,"多选题","下列关于气体灭火系统的联动控制检查，符合规范要求的是（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","气体灭火控制器由防护区内两个独立的感烟火灾探测器自动控制",true,{"key":16,"text":17,"correct":14},"B","气体灭火控制器由防护区内一个独立的感烟火灾探测器和一个独立的感温火灾探测器自动控制",{"key":19,"text":20,"correct":21},"C","气体灭火控制器在接收到符合逻辑关系的两个联动触发信号后，启动该防护区内的声光报警器",false,{"key":23,"text":24,"correct":21},"D","启动气体灭火装置之后，启动设置在防护区入口处表示气体喷洒的火灾声光警报器",{"key":26,"text":27,"correct":14},"E","平时无人工作的防护区设置为无延迟的喷射","ABE","AB正确，气体灭火控制器的自动控制方式应符合下列规定：1应由同一防护区域内两只独立的火灾探测器的报警信号、一只火灾探测器与一只手动火灾报警按钮的报警信号或防护区外的紧急启动信号，作为系统的联动触发信号，探测器的组合宜采用感烟火灾探测器和感温火灾探测器。C错，气体灭火控制器在接收到满足联动逻辑关系的首个联动触发信号后，应启动设置在该防护区内的火灾声光警报器。D错，启动气体灭火装置同时，应启动设置在防护区入口处表示气体喷洒的火灾声光警报器。E正确，平时无人工作的防护区，可设置为无延迟的喷射。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]