[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936433":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},936433,605,1,"单选题","下列关于某建筑的火灾自动报警系统中火灾探测器的检查结果，符合规范要求的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","感烟、感温火灾探测器倾斜安装，且倾角为50°",false,{"key":16,"text":17,"correct":14},"B","感烟、感温火灾探测器底座连接导线留有100mm的余量",{"key":19,"text":20,"correct":21},"C","感烟、感温火灾探测器至墙壁的水平距离0．7m",true,{"key":23,"text":24,"correct":14},"D","感烟火灾探测器设置在镂空面积与总面积的比例为15％格栅吊顶场所时，设置在吊顶上方","A错，探测器宜水平安装，当确实需倾斜安装时，倾斜角不应大于45°。B错，探测器底座的连接导线应留有不小于150mm的余量。C正确，感烟、感温探测器至墙壁、梁边的水平距离不应小于0．5m。D错，感烟火灾探测器在格栅吊顶场所的设置，应符合下列规定：镂空面积与总面积的比例不大于15％时，探测器应设置在吊顶下方。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]