[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936432":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936432,605,2,"多选题","根据《火灾自动报警系统设计规范》（GB50116-2013）的规定，可以作为排烟风机联动触发信号的有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","同一防烟分区内两只感烟探测器",false,{"key":16,"text":17,"correct":14},"B","同一防烟分区内一只感烟探测器和一只感温探测器",{"key":19,"text":20,"correct":21},"C","排烟口开启的动作信号",true,{"key":23,"text":24,"correct":21},"D","排烟窗开启的动作信号",{"key":26,"text":27,"correct":21},"E","排烟阀开启的动作信号","CDE","《火灾自动报警系统设计规范》（GB50116-2013）第4．5．2条：应由排烟口、排烟窗或排烟阀开启的动作信号，作为排烟风机启动的联动触发信号，并应由消防联动控制器联动控制排烟风机的启动。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]