[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936427":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936427,605,2,"多选题","消防设施检测机构对某商场设置的防火卷帘系统进行检测，在检测联动控制功能时，根据现行国家消防技术标准，下列关于设置在疏散通道上的防火卷帘联动控制的说法中，正确的有（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","防火分区内任两只独立的感烟火灾探测器的报警信号应联动控制防火卷帘下降至距楼板面1.8m处",true,{"key":16,"text":17,"correct":14},"B","防火分区内任一只专门用于联动防火卷帘的感烟火灾探测器的报警信号应联动控制防火卷帘下降至距楼板面1.8m处",{"key":19,"text":20,"correct":14},"C","任一只专门用于联动防火卷帘的感温火灾探测器的报警信号应联动控制防火卷帘下降到楼板面",{"key":22,"text":23,"correct":24},"D","任一只防火卷帘附近的手动报警按钮的报警信号应联动控制防火卷帘下降到楼板面",false,{"key":26,"text":27,"correct":14},"E","专门用于联动某个防火卷帘的感温火灾探测器不应少于2只","ABCE","《火灾自动报警系统设计规范》（GB 50116-2013），4.6.3，选项D，防火卷帘手动是用手动控制按钮直接控制升降。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]