[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936425":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936425,605,2,"多选题","在对建筑中由火灾自动报警系统联动启动的雨淋喷水灭火系统进行检测时，应检测雨淋阀组联动控制功能，根据现行国家消防技术标准的规定，下列关于开启雨淋阀组的联动触发信号的说法中，正确的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","同一报警区域内两个及以上独立的感温火灾探测器的报警信号",true,{"key":16,"text":17,"correct":18},"B","同一报警区域内两个及以上独立的感烟火灾探测器的报警信号",false,{"key":20,"text":21,"correct":18},"C","同一报警区域内一个感烟火灾探测器与一个手动火灾报警按钮的报警信号",{"key":23,"text":24,"correct":18},"D","同一报警区域内一个感烟火灾探测器与一个感温火灾探测器的报警信号",{"key":26,"text":27,"correct":14},"E","同一报警区域内一个感温火灾探测器与一个手动火灾报警按钮的报警信号","AE","雨淋系统的联动控制设计应由同一报警区域内两个及两个以上独立的感温火灾探测器或一个感温火灾探测器与一个手动火灾报警按钮的报警信号（“与”逻辑），作为雨淋阀组开启的联动触发信号。消防联动控制器在接收到满足逻辑关系的联动触发信号后，联动控制雨淋阀组的开启。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]