[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936419":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936419,605,2,"多选题","某消防技术服务单位对一大型工业企业内设置的火灾报警系统进行检查，发现如下内容，其中符合国家消防技术标准的是（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","火灾报警控制器与总线采用端子板进行连接，有个别接线端接有2根导线",true,{"key":16,"text":17,"correct":14},"B","消防控制室内火灾报警控制器采用落地安装方式，底部高出地面20cm",{"key":19,"text":20,"correct":14},"C","电缆桥架内敷设的缆式线型感温火灾探测器采用专用接线盒连接",{"key":22,"text":23,"correct":24},"D","电缆桥架内敷设的缆式线型感温火灾探测器弯曲半径为0．1m",false,{"key":26,"text":27,"correct":24},"E","模块箱内安装的模块，个别留有120mm余量的导线","ABC","根据《火灾自动报警系统施工及验收规范》GB 50166—2019 3 端子板的每个接线端，接线不得超过2根，A选项正确；火灾报警控制器、可燃气体报警控制器、区域显示器、消防联动控制器等控制器类设备（以下称控制器）落地安装时，其底边宜高出地（楼）面0．1～0．2m，B选项正确；缆式线型感温火灾探测器应采用连续无接头方式安装，如确需中间接线，必须用专用接线盒连接。探测器安装敷设时不应硬性折弯、扭转，避免重力挤压冲击，探测器的弯曲半径宜大于0．2m，C选项正确，D选项错误；模块的连接导线，应留有不小于150mm的余量，E选项错误。本题答案为ABC。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]