[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936396":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},936396,605,1,"单选题","某消防技术服务机构对施工完毕的火灾自动报警系统进行检查，检查结果符合规范要求的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","点型感烟火灾探测器距离墙壁的水平距离为0．3m",false,{"key":16,"text":17,"correct":14},"B","安装在顶棚上的点型感烟火灾探测器距离空调送风口的水平距离为0．5m",{"key":19,"text":20,"correct":21},"C","在宽度小于3m的内走道顶棚上安装探测器时、宜居中安装，点型感温火灾探测器的安装间距不应超过10m，点型感烟火灾探测器的安装间距不应超过15m，探测器至端墙的距离不应大于安装间距的一半。",true,{"key":23,"text":24,"correct":14},"D","每个报警区域的模块集中设置在配电箱内","根据《火灾自动报警系统施工及验收规范》GB 50166—2019 3.3.6—1 点型感烟火灾探测器至墙壁、梁边的水平距离，不应小于0．5m，A选项错误；根据3.3.6—3，点型感烟火灾探测器至空调送风口最近边的水平距离，不应小于1．5m，至多孔送风顶棚孔口的水平距离，不应小于0．5m，B选项错误；根据3.3.6-4 在宽度小于3m的内走道顶棚上安装探测器时、宜居中安装，点型感温火灾探测器的安装间距不应超过10m，点型感烟火灾探测器的安装间距不应超过15m，探测器至端墙的距离不应大于安装间距的一半。C选项正确；根据《火灾自动报警系统设计规范》GB 50116—20136．8．2，模块严禁设置在配电（控制）柜（箱）内，D选项错误。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]