[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936395":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936395,605,2,"多选题","火灾自动报警系统进行布线时，当管路超过一定长度，应在便于接线处装设接线盒。下列部位应设置接线盒的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","管子长度32m，无弯曲",true,{"key":16,"text":17,"correct":18},"B","管子长度6m，有2个弯曲时",false,{"key":20,"text":21,"correct":14},"C","管子长度21m，有1个弯曲时",{"key":23,"text":24,"correct":18},"D","管子长度15m，有1个弯曲",{"key":26,"text":27,"correct":14},"E","管子长度9m，有3个弯曲","ACE","根据《火灾自动报警系统施工及验收规范》GB 50166—20073．2．8，管路超过下列长度时，应在便于接线处装设接线盒：管子长度每超过30m，无弯曲时；管子长度每超过20m，有1个弯曲时；管子长度每超过10m，有2个弯曲时；管子长度每超过8m，有3个弯曲时。本题答案为ACE。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]