[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936384":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936384,605,2,"多选题","火灾自动报警系统管路超过下列长度时，应在便于接线处装设接线盒（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","管子长度每超过30m，无弯曲时",true,{"key":16,"text":17,"correct":18},"B","管子长度每超过10m，有1个弯曲时",false,{"key":20,"text":21,"correct":14},"C","管子长度每超过10m，有2个弯曲时",{"key":23,"text":24,"correct":14},"D","管子长度每超过8m，有3个弯曲时",{"key":26,"text":27,"correct":18},"E","管子长度每超过8m，有4个弯曲时","ACD","管路超过下列长度时，应在便于接线处装设接线盒： （1）管子长度每超过30m，无弯曲时。 （2）管子长度每超过20m，有1个弯曲时。 （3）管子长度每超过10m，有2个弯曲时。 （4）管子长度每超过8m，有3个弯曲时。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]