[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936383":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},936383,605,1,"单选题","下列关于消防应急照明和疏散指示系统的检查结果，符合规范要求的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","消防应急灯具连接在专门用于该系统的插座上",false,{"key":16,"text":17,"correct":14},"B","安装在侧墙上消防应急灯具其底部距地面1．5m",{"key":19,"text":20,"correct":21},"C","应急照明分配电装置的输出线路可以选择燃烧性能为B1级的电线电缆",true,{"key":23,"text":24,"correct":14},"D","地面安装灯具的供电线路选择耐腐蚀的橡胶电缆，控制线路可选择普通的阻燃耐火电缆","A错，消防应急灯具与供电线路之间不能使用插头连接。B错，消防应急照明灯具在侧面墙上顶部安装时，其底部距地面距离不得低于2m。C正确，应急照明分配电装置的输出线路和集中控制型系统的控制线路选择燃烧性能为B1级电线电缆时，应穿金属管保护。D错，地面安装灯具的供电线路和控制线路均应选择耐腐蚀的橡胶电缆，接线处应有防腐蚀和防潮处理。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]