[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936381":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},936381,605,1,"单选题","下列关于消防应急照明灯具与疏散指示标志灯具安装的做法，不符合消防技术标准的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","消防应急照明灯具安装在顶棚上",false,{"key":16,"text":17,"correct":18},"B","消防应急照明灯具与主电源间的连线采用插头连接",true,{"key":20,"text":21,"correct":14},"C","疏散走道上标志灯具的安装间距为9m",{"key":23,"text":24,"correct":14},"D","消防应急照明灯具采用金属杆吊装在建筑结构件上","消防应急照明灯具最好安装在顶棚或距楼地面2m以上的侧面墙上。消防应急灯具与供电线路之间不能使用插头连接。疏散走道上标志灯具的安装间距不应大于20m，对于袋形走道不应大于10m，在走道转角区不应大于1m。消防应急照明灯具采用金属杆吊装时，吊杆上端固定在建筑结构件上。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]