[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936380":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936380,605,2,"多选题","下列关于应急照明控制器安装的做法，正确的是（ ）。",[11,15,18,21,24],{"key":12,"text":13,"correct":14},"A","安装在墙上的应急照明控制器高度为1．4m",true,{"key":16,"text":17,"correct":14},"B","安装在墙上的应急照明控制器正面操作距离为1．3m",{"key":19,"text":20,"correct":14},"C","应急照明控制器的主电源有明显标志",{"key":22,"text":23,"correct":14},"D","应急照明控制器与其外接备用电源之间直接连接",{"key":25,"text":26,"correct":27},"E","应急照明控制器的导线，留有100mm的余量",false,"ABCD","应急照明控制器在墙上安装时，应急照明控制器的底边距地（楼）面高度为1．3～1．5m，靠近门或侧墙安装时应保证应急照明控制器门的正常开关，正面操作距离不应小于1．2m。落地安装时，其底边宜高出地坪0．1～0．2m，AB选项正确；应急照明控制器的主电源要有明显标志，并应直接与消防电源连接，严禁使用电源插头。应急照明控制器与其外接备用电源之间应直接连接。接地应牢固，并应有明显标志，CD选项正确；引入应急照明控制器的电缆或导线应留有不小于200mm的余量，E选项错误。本题答案为ABCD。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]