[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936369":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},936369,605,1,"单选题","关于某场所设置的应急照明配电箱检查结果中，不符合规范要求的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","宜设置在值班室、设备机房、配电间或电气竖井内",false,{"key":16,"text":17,"correct":14},"B","人员密集场所，每个防火分区应设置独立的应急照明配电箱",{"key":19,"text":20,"correct":14},"C","A型应急照明配电箱的输出回路不应超过8路",{"key":22,"text":23,"correct":24},"D","B型应急照明配电箱的输出回路不应超过60路。",true,"应急照明配电箱的设置应符合下列规定:1）宜设置在值班室、设备机房、配电间或电气竖井内。2） 人员密集场所，每个防火分区应设置独立的应急照明配电箱;非人员密集场所，多个相邻防火分区可设置一个共用的应急照明配电箱。3）防烟楼梯间应设置独立的应急照明配电箱，封闭楼梯间宜设置独立的应急照明配电箱。A型应急照明配电箱的输出回路不应超过8 路， B型应急照明配电箱的输出回路不应超过12路。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]