[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936344":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},936344,605,1,"单选题","消防用电设备的供电线路采用不同的电线电缆时，供电线路的敷设方式也不同，当敷设方式采用直接明敷时，应优先选用的电缆是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","矿物绝缘电缆",true,{"key":16,"text":17,"correct":18},"B","难燃性电缆",false,{"key":20,"text":21,"correct":18},"C","有机绝缘耐火电缆",{"key":23,"text":24,"correct":18},"D","阻燃电线电缆","根据《建筑设计防火规范》GB 50016—2014（2018年版）10．1．10—1，消防配电线路应满足火灾时连续供电的需要，其敷设应符合下列规定：明敷时（包括敷设在吊顶内），应穿金属导管或采用封闭式金属槽盒保护，金属导管或封闭式金属槽盒应采取防火保护措施；当采用阻燃或耐火电缆并敷设在电缆井、沟内时，可不穿金属导管或采用封闭式金属槽盒保护；当采用矿物绝缘类不燃性电缆时，可直接明敷。本题答案为A。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]