[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936342":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},936342,605,1,"单选题","某消防技术服务机构对某商场内的消防供配电系统进行检查，发现下列情况，其中不符合消防技术标准的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","建筑物内设有变电所，消防配电系统在变电所处开始自成系统",false,{"key":16,"text":17,"correct":14},"B","在防烟和排烟风机配电线路的最末一级配电箱处设置自动切换装置",{"key":19,"text":20,"correct":14},"C","采用柴油发电机组作为备用电源，柴油发电机组设置自动和手动启动装置",{"key":22,"text":23,"correct":24},"D","消防配电线路采用有机绝缘耐火电缆，在电气竖井内与非消防配电线路同束敷设",true,"当采用难燃性电缆或有机绝缘耐火电缆时，在电气竖井内或电缆沟内敷设可不穿导管保护，但应采取与非消防用电缆隔离的措施。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]