[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936337":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936337,605,2,"多选题","现对某建筑内设置的防排烟系统进行检查验收，下列检查结果中符合规范要求的是（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","送风机设置在专用机房内，该房间采用耐火极限不低于2．00h的隔墙和1．50h的楼板及甲级防火门与其他部位隔开",true,{"key":16,"text":17,"correct":14},"B","送风管道采用镀锌钢板，测量管道风速为15m／s",{"key":19,"text":20,"correct":21},"C","建筑每层前室设一个常开式加压送风口",false,{"key":23,"text":24,"correct":21},"D","排烟管道采用土建风道，测量管道风速为15m／s",{"key":26,"text":27,"correct":21},"E","测量排烟口至该防烟分区最远点的水平距离为35m","AB","B正确，当采用金属管道时，管道风速不应大于20m／s。 C错，前室、合用前室应每层设置一个常闭式加压送风口，并应设置手动开启装置。 D错，排烟管道必须采用不燃材料制作，且不应采用土建风道。当采用金属风道时，管道风速不应大于20m／s，当采用非金属材料风道时，不应大于15m／s。 E错，排烟口应尽量设置在防烟分区的中心部位，且排烟口至该防烟分区最远点的水平距离不应超过30m。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]