[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936335":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},936335,605,1,"单选题","对某公共建筑内的防排烟系统进行安装检查，根据《建筑防烟排烟系统技术标准》GB51251—2017的相关要求，下列关于风管安装要求的做法中，不正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","金属风管采用法兰连接时，其螺栓孔的间距不得大于150mm",false,{"key":16,"text":17,"correct":14},"B","非金属风管采用法兰连接时，其螺栓孔的间距不得大于120mm",{"key":19,"text":20,"correct":21},"C","金属风管应以板材连接的密封为主，可辅以密封胶嵌缝或其他方法密封，密封面宜设在风管的负压侧",true,{"key":23,"text":24,"correct":14},"D","金属排烟风管的隔热层应采用厚度不小于40mm的不燃绝热材料","根据《建筑防烟排烟系统技术标准》GB 51251-20176．3．1—2，金属风管采用法兰连接时，其螺栓孔的间距不得大于150mm，A选项正确；根据6．3．2—2，非金属风管采用法兰连接时，其螺栓孔的间距不得大于120mm，B选项正确；根据6．3．1—2，风管应以板材连接的密封为主，可辅以密封胶嵌缝或其他方法密封，密封面宜设在风管的正压侧，C选项错误：根据6．3．1—5，金属排烟风管的隔热层应采用厚度不小于40mm的不燃绝热材料，D选项正确。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]