[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936322":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},936322,605,1,"单选题","某消防检测维保机构对某建筑的防排烟系统进行维保检测，以下不符合规范要求的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","设置在房间吊顶内的排烟管道，耐火极限为0．5h",false,{"key":16,"text":17,"correct":18},"B","常闭送风口的手动驱动装置距离楼地面1．2m",true,{"key":20,"text":21,"correct":14},"C","排烟口设置在靠近顶棚的墙面上",{"key":23,"text":24,"correct":14},"D","排烟机房中排烟风机距离墙壁0．7m","根据《建筑防烟排烟系统技术规范》GB 51251—20174．4．8—3，水平设置的排烟管道应设置吊顶内，其耐火极限不应低于0．5h，A选项正确；根据6．4．3，常闭送风口、排烟阀或排烟口的手动驱动装置应固定安装在明显可见、距楼地面1．3m～1．5m之间便于操作的位置，B选项错误；根据4．4．12—1，排烟口宜设置在顶棚或靠近顶棚的墙面上，C选项正确；根据4．4．5，排烟风机应设置在专用机房内，且风机两侧应有600mm以上的空间，D选项正确。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]