[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936318":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936318,605,2,"多选题","消防设施检测机构对某商场的防排烟系统进行检测验收，检测记录的下列结果中，不符合现行国家消防技术标准要求的是（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","手动打开某防烟分区内的排烟阀，对应的排烟风机能联动启动",false,{"key":16,"text":17,"correct":14},"B","模拟火灾，发出报警信号后，相关部位的送风口和送风机启动",{"key":19,"text":20,"correct":14},"C","手动关闭排烟风机入口处的排烟防火阀，排烟风机停止运转",{"key":22,"text":23,"correct":24},"D","在挡烟垂壁附近的一只感烟探测器附近模拟烟气，挡烟垂壁降落",true,{"key":26,"text":27,"correct":24},"E","经测量，加压送风口处的风速为8.5m\u002Fs","DE","选项D，挡烟垂壁应当是附近两个独立的感烟探测器发出信号后动作。选项E，加压送风口的风速不宜大于7m\u002Fs。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]