[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936316":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936316,605,2,"多选题","某消防技术服务机构对已完工的防烟排烟系统进行检查，下列有关排烟防火阀设置位置的检查结果中，符合规范要求的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","排烟风机的出口处设置了排烟防火阀",false,{"key":16,"text":17,"correct":18},"B","垂直风管与每层水平风管交接处的水平管段上设置了排烟防火阀",true,{"key":20,"text":21,"correct":14},"C","送风机的入口处设置了排烟防火阀",{"key":23,"text":24,"correct":18},"D","穿越防火分区处设置了排烟防火阀",{"key":26,"text":27,"correct":18},"E","一个排烟系统中负担多个防烟分区的排烟支管上","BDE","根据《建筑防烟排烟系统技术标准》GB 51251—20174．4．10，排烟管道下列部位应设置排烟防火阀： 1）垂直风管与每层水平风管交接处的水平管段上。 2）一个排烟系统负担多个防烟分区的排烟支管上。 3）排烟风机入口处。 4）穿越防火分区处。 排烟风机的入口处应设置排烟防火阀，A选项错误；排烟防火阀安装在机械排烟系统的管道上，防烟系统的管道上不需要设置排烟防火阀，C选项错误。本题答案为BDE。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]