[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936306":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936306,605,2,"多选题","对某公共建筑内的防烟排烟系统调试，根据《建筑防烟排烟系统技术标准》GB 51251—2017的相关要求，下列关于调试的要求做法中，正确的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","当任何一个常闭送风口开启时，相应的送风机均应能联动启动",true,{"key":16,"text":17,"correct":18},"B","手动开启风机，风机应正常运转3．0h，叶轮旋转方向应正确、运转平稳",false,{"key":20,"text":21,"correct":14},"C","对楼梯间和前室的机械加压送风系统调试应单独分别进行，且互不影响",{"key":23,"text":24,"correct":14},"D","有补风要求的机械排烟场所，当火灾确认后，补风系统应启动",{"key":26,"text":27,"correct":14},"E","当任何一个常闭排烟阀或排烟口开启时，排烟风机均应能联动启动","ACDE","根据《建筑防烟排烟系统技术标准》GB 51251—20177．3．1—1，当任何一个常闭送风口开启时，相应的送风机均应能联动启动，A选项正确；根据7．2．5—1，手动开启风机，风机应正常运转2．0h，叶轮旋转方向应正确、运转平稳、无异常振动与声响，B选项错误；根据7．2．6—2，对楼梯间和前室的机械加压送风系统调试应单独分别进行，且互不影响，C选项正确；根据7．3．2—3，有补风要求的机械排烟场所，当火灾确认后，补风系统应启动，D选项正确；根据7．3．2—1，当任何一个常闭排烟阀或排烟口开启时，排烟风机均应能联动启动，E选项正确。本题答案ACDE。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]