[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936305":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936305,605,2,"多选题","防烟系统是防止火灾烟气在楼梯间、前室、避难层筹空间聚集的系统，下列关于建筑物防烟方式的选择，设计方案不正确的有（ ）",[11,15,18,21,24],{"key":12,"text":13,"correct":14},"A","某一类高层住宅楼，楼梯间采用自然通风，项部未设置开口，合用前室采用机械加压送风，风口设置在顶部",true,{"key":16,"text":17,"correct":14},"B","某公寓楼60m,合用前室采用敞开的阳台，楼梯间未设置防烟设施",{"key":19,"text":20,"correct":14},"C","某住宅楼80m,采用剪刀楼梯间，共用前室与消防电梯前室合用，剪刀楼梯间与合用前室均采用自然通风",{"key":22,"text":23,"correct":14},"D","某地下商业场所划分若干防火分区，其避难走道仅服务一个防火分区且仅设置一个安全出口，仅在前室设置了机械加压送风系统",{"key":25,"text":26,"correct":27},"E","某超高层酒店，避难层四周设置可开启外窗，未设置机械加压送风系统",false,"ABCD","楼梯间采用自然通风，顶部应设置不小于1m2开口，A错误。公寓楼超过50m,楼梯间前室分别设置机械加压送风，B错误。三合一前室，应设置机械加压送风系统，C错误。避难走道仅设置一个安全出口且长度\u003C30m时，可仅在前室设置了机械加压送风系统，D错误。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]