[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936304":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936304,605,2,"多选题","在对某高度为60m的办公楼设置的防烟排烟系统检查时获取的下列信息中，符合现行国家技术标准的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","防烟楼梯间内采用直灌式加压送风系统",false,{"key":16,"text":17,"correct":18},"B","防烟楼梯间前室内设置常闭式送风口",true,{"key":20,"text":21,"correct":18},"C","机械加压送风管道井壁上的检修门为乙级防火门",{"key":23,"text":24,"correct":14},"D","送风机与排烟风机合用机房，机房内设置自动喷水灭火系统",{"key":26,"text":27,"correct":14},"E","一个排烟系统负担多个防烟分区，只在排烟风机入口总管上设置了排烟防火阀","BC","根据《建筑防烟排烟系统技术标准》GB 51251—20173．3．3，大于50m的建筑的楼梯间不能采用直灌式加压送风，A选项错误；根据3．1．7，设置机械加压送风系统的场所，楼梯间应设置常开风口，前室应设置常闭风口，B选项正确；根据3．3．9，机械加压送风系统的管道井应采用耐火极限不低于1．00h的隔墙与相邻部位分隔，当墙上必须设置检修门时应采用乙级防火门，C选项正确；根据3．3．5—5，送风机应设置在专用机房内，D选项错误；根据4．4．10—2，一个排烟系统负担多个防烟分区的排烟支管上应设置排烟防火阀，E选项错误。本题答案为BC。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]