[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936300":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},936300,605,1,"单选题","在对建筑进行防烟分区检查时，应注意检查挡烟垂壁的安装是否满足现行国家消防技术标准的要求。下列关于活动挡烟垂壁安装的说法中，正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","活动挡烟垂壁与建筑结构墙面的缝隙不应大于70mm",false,{"key":16,"text":17,"correct":14},"B","两块或两块以上的挡烟垂帘组成的连续性挡烟垂壁，各块之间的缝隙不应大于20mm",{"key":19,"text":20,"correct":14},"C","活动挡烟垂壁与建筑结构墙面的缝隙不应大于80mm",{"key":22,"text":23,"correct":24},"D","两块或两块以上的挡烟垂帘组成的连续性挡烟垂壁，各块之间不应有缝隙，搭接宽度不应小于100mm",true,"根据《建筑防烟排烟系统技术标准》GB 51251—20176．4．4—2，活动挡烟垂壁与建筑结构（柱或墙）面的缝隙不应大于60mm，由两块或两块以上的挡烟垂帘组成的连续性挡烟垂壁，各块之间不应有缝隙，搭接宽度不应小于100mm。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]