[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936298":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},936298,605,1,"单选题","对某建筑防烟排烟系统进行检查时，符合现行国家工程消防技术标准要求的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","加压送风管道采用难燃材料制作",false,{"key":16,"text":17,"correct":14},"B","安装排烟管道时，应采取隔热防火措施或与可燃物保持不小于100 mm的距离",{"key":19,"text":20,"correct":21},"C","排烟风机应保证在280℃的环境条件下能连续工作不少于30 min",true,{"key":23,"text":24,"correct":14},"D","固定式挡烟垂壁可采用隔墙、楼板下不小于100 mm的梁或吊顶下凸出不小于100 mm的不燃烧体","防烟排烟系统的加压送风管道采用不燃材料制作；安装排烟管道时，应采取隔热防火措施或与可燃物保持不小于150 mm的距离；排烟风机应保证在280℃的环境条件下能连续工作不少于30 min；固定式挡烟垂壁可采用隔墙、楼板下不小于500 mm的梁或吊顶下凸出不小于500 mm的不燃烧体。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]