[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936295":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},936295,605,1,"单选题","对某建筑内设置的排烟口进行检查，下列检查结果中，符合现行国家消防技术标准的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","建筑内设有自动喷水灭火系统，排烟口与该排烟口所在防烟分区内最远点的水平距离为37．5m",false,{"key":16,"text":17,"correct":18},"B","测试排烟口的风速为8m／s",true,{"key":20,"text":21,"correct":14},"C","设置在走道侧墙上的排烟口距离防烟楼梯间的门的距离为0．5m",{"key":23,"text":24,"correct":14},"D","房间的吊顶采用难燃材料制作，排烟口设置在吊顶内并通过吊顶上部空间进行排烟","根据《建筑防烟排烟系统技术标准》GB 51251—20174．4．12，排烟口的设置应经计算确定，且防烟分区内任一点与最近的排烟口之间的水平距离不应大于30m，与是否设置自喷无关，A选项错误；据4．4．12—7，排烟口的风速不宜大于10m／s，B选项正确：根据4．4．12—5，排烟口的设置宜使烟流方向与人员疏散方向相反，排烟口与附近安全出口相邻边缘之间的水平距离不应小于1．5m，C选项错误；根据4．4．13—1，当排烟口设在吊顶内且通过吊顶上部空间进行排烟时，吊顶应采用不燃材料，且吊顶内不应有可燃物，D选项错误。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]