[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936281":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},936281,605,1,"单选题","某学校宿舍长度为40 m，宽度为13 m，建筑层数6层，建筑高度21 m，设有室内消火栓系统。宿舍楼每层设置15间宿舍，每间宿舍学生人数为4人。每层中间沿长度方向设2 m宽的走道。该楼每层灭火器布置做法中，符合《建筑灭火器配置设计规范》（GB50140）要求的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","从距走道端部5 m处开始每10 m布置1具MF／ABC5灭火器",true,{"key":16,"text":17,"correct":18},"B","在走道尽端各5 m处分别布置2具MF／ABC4灭火器",false,{"key":20,"text":21,"correct":18},"C","在走道尽端各5 m处分别布置2具MF／ABC5灭火器",{"key":23,"text":24,"correct":18},"D","从距走道端部5 m处开始每隔10 m布置1具MS／Q6灭火器","根据《建筑灭火器配置设计规范》（GB 50140），该宿舍床位数为15×4×6=360（个），属于严重危险级，单具灭火器最小配置灭火级别应为3A。MF／ABC4为2A，故选项B错误。MS／Q6为1A，故选项D错误。A类火灾场所中，灭火器最大保护距离为15 m，故选项C错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]