[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936272":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936272,605,2,"多选题","某办公楼物业公司对建筑内配置的灭火器进行检查时发现如下情况，应进行送修处理的有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","楼道内压力表指针指向红区的干粉灭火器",true,{"key":16,"text":17,"correct":14},"B","电子计算机房内出厂期刚满7年的二氧化碳灭火器",{"key":19,"text":20,"correct":21},"C","筒体严重变形的灭火器",false,{"key":23,"text":24,"correct":14},"D","开启使用过的灭火器",{"key":26,"text":27,"correct":21},"E","楼道内出厂期刚满4年的干粉灭火器","ABD","根据《建筑灭火器配置验收及检查规范》GB 50444—20085．3．1，存在机械损伤、明显锈蚀、灭火剂泄露、被开启使用过或符合其他维修条件的灭火器应及时进行维修，AD选项正确；根据5．3．2，二氧化碳灭火器出厂期满5年首次维修以后每满2年维修一次，干粉灭火器出厂期满5年首次维修以后每满2年维修一次，B选项正确，E选项错误；根据5．4．2—2，筒体明显变形的灭火器应报废，C选项错误。本题答案为ABD。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]