[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936266":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936266,605,2,"多选题","在对某大型商业综合体内配置的灭火器进行验收时发现以下缺陷项，其中属于重缺陷项的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","地下一层超市配置了规格型号为MF／ABC2灭火器",false,{"key":16,"text":17,"correct":18},"B","部分灭火器箱被上锁",true,{"key":20,"text":21,"correct":14},"C","五层电影院区域灭火器设置数量不足",{"key":23,"text":24,"correct":18},"D","有视线障碍的设置点，未设置指示灭火器位置的发光标志",{"key":26,"text":27,"correct":14},"E","地下配电室内设置在托架上的灭火器距地高度1．6m","BD","根据《建筑灭火器配置验收及检查规范》GB 50444—2008附录B，灭火器的类型、规格、灭火级别和配置数量不符合建筑灭火器配置设计要求属于严重缺陷项，AC选项错误；灭火器箱被上锁属于重缺陷项，B选项正确；有视线障碍的设置点设置灭火器时，未在醒目的地方设置指示灭火器位置的发光标志属于重缺陷项，D选项正确；设置在托架上的灭火器，灭火器顶部离地面距离大于1．5m属于轻缺陷项，E选项错误。本题答案为BD。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]