[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936228":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},936228,605,1,"单选题","对某单位的干粉灭火系统组件进行检测，下列关于系统组件的检测结果，不符合规范要求的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","干粉储存容器灭火剂的装量系数为0．9，增压时间为25s",true,{"key":16,"text":17,"correct":18},"B","驱动气体储瓶及其充装系数符合国家现行标准《气瓶安全监察规程》的规定",false,{"key":20,"text":21,"correct":18},"C","驱动气体选用氮气",{"key":23,"text":24,"correct":18},"D","驱动压力小于干粉储存容器的最高工作压力","根据《干粉灭火系统设计规范》GB 50347—20045．1．1—2，干粉储存容器设计压力可取1．6MPa或2．5MPa压力级；其干粉灭火剂的装量系数不应大于0．85；其增压时间不应大于30s，A选项错误；根据5．1．1—1，驱动气体储瓶及其充装系数应符合国家现行标准《气瓶安全监察规程》的规定，B选项正确；根据5．1．2，驱动气体应选用惰性气体，宜选用氮气；驱动压力不得大于干粉储存容器的最高工作压力，CD选项正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]