[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936211":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},936211,605,1,"单选题","干粉灭火系统组件安装完毕后需要进行调试，其中模拟喷放试验应采用干粉灭火剂和自动启动方式，干粉用量不少于设计用量的（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","10%",false,{"key":16,"text":17,"correct":14},"B","15%",{"key":19,"text":20,"correct":14},"C","20%",{"key":22,"text":23,"correct":24},"D","30%",true,"模拟喷放试验采用干粉灭火剂和自动启动方式，干粉用量不少于设计用量的30%；当现场条件不允许喷放干粉灭火剂时，可采用惰性气体；采用的试验气瓶需与干粉灭火系统驱动气体储瓶的型号规格、阀门结构、充装压力、连接与控制方式一致。试验时应保证出口压力不低于设计压力。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]