[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936209":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},936209,605,1,"单选题","对于储气瓶型干粉灭火系统，当采用全淹没灭火系统时，喷头的最大安装高度不大于（ ）m，当采用局部应用系统时，喷头最大安装高度不大于（ ）m。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","7，6",false,{"key":16,"text":17,"correct":18},"B","8，7",true,{"key":20,"text":21,"correct":14},"C","8，6",{"key":23,"text":24,"correct":14},"D","7，5","对于储压型系统，当采用全淹没灭火系统时，喷头的最大安装高度不大于7m：当采用局部应用系统时，喷头最大安装高度不大于6m；对于储气瓶型系统，当采用全淹没灭火系统时，喷头的最大安装高度不大于8m；当采用局部应用系统时，喷头最大安装高度不大于7m。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]