[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936208":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},936208,605,1,"单选题","干粉灭火系统进行气密性试验时，达到试验压力，关断试验气源3min内压力降不超过试验压力的（ ）为合格。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","10％",true,{"key":16,"text":17,"correct":18},"B","20％",false,{"key":20,"text":21,"correct":18},"C","30％",{"key":23,"text":24,"correct":18},"D","40％","气密性试验：干粉输送管道进行气密性试验时，对干粉输送管道，试验压力为水压强度试验压力的2／3；对气体输送管道，试验压力为气体最高工作储存压力。进行气密性试验时，应以不大于0．5MPa／s的升压速率缓慢升压至试验压力。关断试验气源3min内压力降不超过试验压力的10％为合格。本题答案为A。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]