[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936198":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},936198,605,1,"单选题","消防设施检测机构对某单位内设置的全淹没干粉系统进行检测，关于防护区及系统功能检查的结果中，不符合现行国家消防技术标准要求的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","干粉喷射时间为50s",true,{"key":16,"text":17,"correct":18},"B","灭火剂设计浓度为0．7kg／m3",false,{"key":20,"text":21,"correct":18},"C","防护区吊顶的耐火极限为0．5h",{"key":23,"text":24,"correct":18},"D","防护区的围护结构及门、窗的耐火极限为1．00h","根据《干粉灭火系统设计规范》GB 50347—20043．2．3，全淹没灭火系统的干粉喷射时间不应大于30s，A选项错误；根据3．2．1，全淹没灭火系统的灭火剂设计浓度不得小于0．65kg／m3，B选项正确；根据3．1．2—2，防护区的围护结构及门、窗的耐火极限不应小于0．50h，吊顶的耐火极限不应小于0．25h；围护结构及门、窗的允许压力不宜小于1200Pa，CD选项正确。本题答案为A。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]