[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936197":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},936197,605,1,"单选题","某单位一封闭防护区采用两套预制干粉灭火系统进行全淹没保护，消防设施检测机构对该系统进行检测，结果如下，其中不符合现行国家消防技术标准要求的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","装置管道长度为15m",false,{"key":16,"text":17,"correct":18},"B","喷放灭火剂时，不能自动关闭的开口设置在防护区底部",true,{"key":20,"text":21,"correct":14},"C","预制灭火装置未设机械应急操作启动方式",{"key":23,"text":24,"correct":14},"D","两套装置响应时间差为1s","根据《干粉灭火系统设计规范》GB 50347—20043．4．1，预制灭火装置管道长度不得大于20m，A选项正确；根据3．1．2—1，喷放干粉时不能自动关闭的防护区开口，其总面积不应大于该防护区总内表面积的15％，且开口不应设在底面，B选项错误；根据6．0．5，预制灭火装置可不设机械应急操作启动方式，C选项正确；根据3．4．3，一个防护区或保护对象所用预制灭火装置最多不得超过4套，并应同时启动，其动作响应时间差不得大于2s，D选项正确。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]