[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-936160":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},936160,605,2,"多选题","某消防检测技术服务人员在对某储罐区泡沫灭火系统进行调试时，发现泡沫产生器无法发泡，下列关于无法发泡原因的分析，正确的是（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","泡沫产生器损坏",true,{"key":16,"text":17,"correct":14},"B","泡沫液失效",{"key":19,"text":20,"correct":14},"C","泡沫产生器吸气口被异物堵塞",{"key":22,"text":23,"correct":24},"D","高位消防水箱压力不足",false,{"key":26,"text":27,"correct":24},"E","消防水池的容积过大","ABC","根据泡沫产生器的工作原理可知，无法发泡或发泡不正常的原因可能有泡沫产生器吸气口被异物堵塞、泡沫液失效、混合比不满足要求或泡沫产生器本身质量就有问题等。消防水池的有效容积与高位消防水箱压力不足与泡沫产生器无法发泡或发泡不正常的原因无关。本题答案为ABC。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]